What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Model
REP-MP20T2-275-3S
The SPD according to IEC/EN 61643-11
T2
Response time(t.)
25ns
Maximum continuous voltage(Uc)
275Vac
Impulse discharge current Iimp (10/350μs) (N-PE)
12.5kA
Nominal discharge current(8/20μs) ln(L-PE, N-PE)
20kA
Maximum discharge current(8/20μs) lmax(L-PE, N-PE)
40kA
Voltage protection level Up @ln
1.2kV
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
385V/5sec.
Remote alarm contact
NO/NC/C, isolated from C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm² or #16AWG
The minimum cross-sectional area of installation
1.5mm² solid/flexible
The maximum cross-sectional area of installation
25mm² flexible
Operating temperature range
-40℃~+80℃
Work/Fault indicator
Green: Normal ; Red: Failure
Installation
35mm DIN rail, according to EN 60715
Shell material
35mmDINrail,according to EN 60715
The installation location
Red thermoplastic material ,UL 94v-0
Degree of protection
IP20
Size
4 modules
Certification
TUV
SEND INQUIRY
REP-MP20T2-275-3S
Dimension drawing(mm)
Basic circuit diagram