What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Type
REP-MP20T2-XXX-XS
The SPD according to IEC 61643-1/11
II/T2
Maximum continuous voltage Uc
440Vac; 385Vac; 320Vac; 275Vac; 150Vac
Impulse discharge current limp(10/350μs)(N-PE)
12.5kA; / ; 12.5kA ; / ; 12.5kA
Nominal discharge current(8/20μs)In
20kA
Maximum discharge current(8/20μs) Imax
40kA
Voltage protection level Up@In
≤2.0kV; ≤1.8kV; ≤1.5kV; ≤1.2kV; ≤1.1kV
Response time(t.)
25ns
Recommend backup fuse
16A gL/gG
Temporary overvoltage(TOV)Ut
580V/5sec.; 440V/5sec.; 440V/5sec.; 385V/5sec.; 210V/5sec.;
Operating temperature range
-40℃~+80℃
The minimum cross-sectional area of installation
1.5mm² solid/flexible
The maximum cross-sectional area of installation
25mm² solid/flexible
Installation
35mm DIN rail, according to EN 60715
Remote alarm contact
NO/NC/C, Isolated form C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A;75V/0.5A
Remote alarm contact connecting wire
Max.1.5mm² or#16AWG
Degree of protection
IP20
Failure indication
Green: Normal ; Red: Failure
Enclosure material
Red thermoplastic material; UL94 V-0
The installation location
Indoor
Degree of protection
IP20
Size
1 modules; 8 modules; 4 modules; 2 modules; 2 modules
Certification
TUV
18mm(1P) 36mm(2P) 54mm(3P)
72mm(4P)
144mm(8P)