SPD for low voltage Transformer

PRODUCT DETAILS

Features

  • REP-MP40/2P adopts UL certified MOV as the key component.
  • Max discharge current Imax(8/20μs) at each path(L-PE;N-PE).
  • Easy installation, Sealed well for water-proof and inflaming retarding.
  • Suitable for harsh outdoor environment.

  • Function optional: failure indicator; remote contact monitoring.

Datasheet

Model

REP-MP40-240/2P

REP-MP40-480/2P                 

Standard

UI14494th:IEC61643-11:2011 

UI14494th:IEC61643-11:2011

Frequency

50/60HZ

50/60HZ

Maximum continuous voltage (Uc)

240Vac

480Vac

Nominal discharge current(8/20μs)ln

5kA

5kA

Maximum discharge current(8/20μs)lmax                   

40kA

40kA

Impulse voltage(1.2/50μs) Uoc

10kV

10kV

Voltage protection level(Up)

@5kA

<1.2kV

<1.6kV

@20kA

<1.8kV

<2.2kV

Leakage current (IL)

<0.1mA

<0.1mA

Response time

≤25ns

≤25ns

Isolation voltage

6KV rms

6KV rms

Temporary over voltage TOV

335Vac, 5s

670Vac, 5s

Operating temperature range

-40℃~+85℃

Work status

Failure indication; Remote alarm contact optional

Installation wire

Phase & Neutral line: black; Neutral Earth line: white    

Wire specification

UI1015 Certified, 10AWG,50cm

For mounting on

Bolt fixing

Enclosure material

304 Stainless steel

Degree of protection

IP68

Seal material

Epoxy resin


Application

REP-MP40/2P is installed outdoor at the low-voltage side of transformer to protect the transformer avoiding failure and damage in case of low voltage surge and over voltage occurs.



 

SEND INQUIRY
GENERAL LOOK

                               

REP-MP40-240/2P-3         REP-MP40-240/2P-4              REP-MP40-480/2P-3        REP-MP40-480/2P-4

Dimension drawing(mm)


Basic circuit diagram



Related Product