SPD for Outdoor Transformer (2P Series)

PRODUCT DETAILS

Features

  • REP-MP40/2P adopts UL certified MOV as the key component.
  • Max discharge current Imax(8/20μs) 40kA at each path(L-PE;N-PE).
  • Easy installation, with 60cm connection wire, connect directly to the phase and neutral (or ground) on the LV side of the transformer, and the arrester has a voltage range of 240V to 480V (MCOV of 240V rms and 480rms).
  • Sealed well for water-proof and inflaming retarding, suitable for harsh outdoor environment.

Datasheet

Model REP-MP40-240-2P-3S  
REP-MP40-480-2P-3S 
Standard
UL1449 4th;IEC61643-11:2011
UL1449 4th;IEC61643-11:2011
Frequency
50/60Hz
50/60Hz
Power system(Un)
120/240Vac
240/480Vac
MCOV
240Vrms
480Vrms
Maximum continuous voltage(Uc)
240Vac
480Vac
Nominal discharge current(8/20μs)In   
5kA
5kA
Maximum discharge current(8/20μs)Imax
40kA
40kA
Impulse voltage(1.2/50μs)(Uoc)
10kV
10kV
Voltage protection level(Up)@5kA
<1.2kV
<1.6kV
Voltage protection level(Up)@20kA
<1.8kV
<2.2kV
Leakage current (IL)
<0.1mA
<0.1mA
Response time
≤25ns
≤25ns
Isolation voltage
6kV rms
6kV rms
Temporary over voltage (TOV)
335Vac,5s
670Vac,5s
Operating temperature range
-40℃~+85 ℃ 
Work status
Light-off: Normal ; Light-on: Failure. (Failure light optional)
Installation wire
Black(L/N):2 wires; White(PE):1 wire
Wire specification
UL1015 Certified, 10AWG,60cm
For mounting on
Bolt fixing
Enclosure material
304 Stainless steel
Degree of protection
IP68
Seal material
Epoxy resin





 

SEND INQUIRY
GENERAL LOOK

REP-MP40/2P(S) Series

Dimension drawing(mm)


Basic circuit diagram



Related Product
HomeEmailContact