What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Type
REP-MP10T3-275-XS
REP-SP230T3-275-XS
The SPD according to IEC/EN 61643
1II/T3
11I/T3
Nominal AC voltage(Un)
230Vac
230Vac
Maximum continuous voltage(Uc)
275Vac
275Vac
Nominal discharge current (8/20μs)ln
10kA
5kA
Maximum discharge current (8/20μs)lmax
20kA
10kA
Voltage protection level(Up)
≤1.2kV
≤1.0kV
Response time
25ns
Operating temperature range
-40℃~+80℃
Remote alarm contact
Remote alarm contact optional
Degree of protection
IP20
Failure indication
Green: Normal ; Red: Failure
Light-off: Normal ; Light-on: Failure
Enclosure material
Thermoplastic; extinguishing degree UL94-V0
Technical feature
Y circuit, small size, offering full protection
SEND INQUIRY
Dimension drawing(mm)2P
Basic circuit diagram