Surge Protectors for AC Power Supply System (T2)

PRODUCT DETAILS

Features

  • Type2 surge protector comply with IEC 61643-11.
  • Low voltage protection level.
  • Reliable supervision due to double integrated disconnection devices.
  • Optional to use without a fuse.
  • Pluggable design, 1+1 protection mode.
  • Remote alarm terminal optional.

Datasheet

Model
REP-MP40T2-275-XS
The SPD according to IEC 61643-1/-11
II/T2
Maximum continuous voltage Uc
275Vac
Impulse discharge current Iimp (10/350μs)(N-PE)
15kA
Nominal discharge current(8/20μs)In
40kA
Maximum discharge current(8/20μs) Imax
80kA
Voltage protection level (Up)@In
1.5kV
Voltage protection level Up [N-PE]
≤1.8kV
Response time(t.)
25ns
Temporary overvoltage(TOV) UT
385V/5sec.
Operating temperature range
-40℃~+80℃
The minimum cross-sectional area of installation
1.5mm² solid/flexible
The maximum cross-sectional area of installation
25mm² solid/flexible
Installation 35mm DIN rail, according to EN  60715
Remote alarm contact
NO/NC/C, Isolated Form C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A;75V/0.5A
Remote alarm contact connecting wire
Max.1.5mm² or#16AWG
Degree of protection
IP20
Work/Fault indicator
Green: Normal ; Red: Failure
Enclosure material
Red thermoplastic material; UL94 V-0
Technical feature
Double integrated disconnection devices with double protections  
The installation location
IP20
Size 4/6/8/16 modules




 

SEND INQUIRY
GENERAL LOOK

                 

36mm(2P)                                                                72mm(4P)                                                                 108mm(6P)            

 144mm(8P)


144mm(8P)

             

Dimension drawing(mm)2P


Basic circuit diagram