Power Surge Protector (Class C / Type2)

PRODUCT DETAILS

Features

  • Type2 surge protector comply with IEC61643-11.
  • Low voltage protection level.
  • Reliable supervision due to double integrated disconnection devices.
  • Optional to use without a fuse.
  • Remote alarm terminal optional.

Datasheet

Model REP-MP40
REP-MP60
REP-MP40NPE
REP-MP60NPE
The SPD according to IEC61643:11
II/T2
II/T2
II/T2
II/T2
Nominal AC voltage (Un)
230/400VAC
230/400VAC
230/400VAC
230/400VAC
Maximum continuous voltage (Uc)
385VAC
385VAC
385VAC
385VAC
Nominal discharge current (8/20μs)In
40kA
60kA
40kA
60kA
Maximum discharge current (8/20μs)Imax
80kA
120kA
80kA
120kA
Voltage protection level (Up)
1.8kV
1.8kV
2.0kV
2.5kV
Response time
25ns
25ns
100ns
100ns
Operating temperature range
-40℃~+80℃
The minimum cross-sectional area of installation
1.5mm² solid/flexible
The maximum cross-sectional area of installation
25mm² solid/flexible
Remote alarm contact
Remote alarm contact optional
Degree of protection
IP20
Failure indication
Green: Normal ; Red: Failure
Enclosure material
Flame retardant material UL94-V0

Installation location

Standard

1. IEC 61643:11-2016
2. UL 1449 4th

     


Side (mm)                                                                                        Front (mm)(4P)


Diagram (3+1)




 

SEND INQUIRY
GENERAL LOOK

                

36mm(2P) (L-N/PE) (N-PE)                                                72mm(4P) (1+1) (2+0)                                                       108mm(6P) (3+0)

144mm(8P)  (3+1) (4+0)

         


Installation Diagram


Installation Details

Installation



Failure Indication



       




Related Product