Surge Protector for PV1200

PRODUCT DETAILS

Features

  • Combined disconnection and short-circuiting device with safe electrical isolation in the protection module.
  • Reliable supervision due to dual integrated disconnection devices.
  • Safe replacement of protection modules with arc extinguish due to integrated d.c. fuse.
  • Enough safety distance with creepage distance more than 30mm.

Datasheet

Model
REP-PV1200
The SPD according to IEC/EN 61643-11 T2
Response time
≤25ns
The largest PV voltage[DC+→DC-] Ucpv
≤1200V
The largest PV voltage[(DC+/DC-)→PE] Ucpv
≤1200V
Short circuit tolerance (Iscpv)
2000A
Nominal discharge current(8/20μs) [(DC+/DC-)→PE] In
20kA
Maximum discharge current(8/20μs) lmax(L-PE, N-PE)
40kA
Total discharge current(8/20μs) [(DC+/DC-)→PE] Itotal
80 KA
Total discharge current(10/350μs) [(DC+/DC-)→PE] Itotal
4.5kA
Lightning Impulse Current (10/350μs) [(DC+/DC-)->PE) (Iimp)
6.25kA
Voltage protection level(Up)
≤4.5kV
Recommended series connection overcurrent protector
63A/35KA
Leakage current
≤10μΑ
Internal overheating circuit breaker
Built-in       
Operating temperature range  
-40℃...+80℃
Work/Fault indicator Green: Normal ; Red: Failure
Connecting wire
≥4mm²
Installation
35mm DIN rail, according to EN 60715
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
IP20
Size
4 modules




 

SEND INQUIRY
GENERAL LOOK

                   REP-PV1200






Related Product