T2 Surge Protector for PV

PRODUCT DETAILS

Features

  • Type2 surge protector comply with IEC61643-11.
  • Reliable supervision due to double integrated disconnection devices.
  • Low voltage protection level.
  • Optional to use without a fuse.
  • Pluggable design, 4+0 protection mode.
  • Remote alarm terminal optional

Datasheet

Model
REP-MP20T2-385-4S
The SPD according to IEC/EN 61643-11
II/T2
Energy coordination with termini equipment (≤5m)
T2
Response time
≤25ns
Maximum continuous voltage(Uc)
385Vac
Nominal discharge current(8/20μs) ln
20kA
Maximum discharge current(8/20μs) lmax
40kA
Voltage protection level Up @ln
≤1.8kV
Follow current extinguishing capability a.c. Ifi
25kA rms
Follow current limitation/Selectivity
No tripping of a 32 A gG fuse up to 25kArms(prosp)
Temporary overvoltage (TOV)(L-N)(UT)-Characteristic
440V/5sec
Let-Through-Energy in combination with an MOV S20K275(Iimp=2.5...25kA) 
<0.5J
Remote alarm contact 
NO/NC/C, Isolated Form C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm²  or #16AWG
Operating temperature range  
-40℃~+80℃
Fault indicator
Green: Normal ; Red: Failure
Cross-sectional area(min)
2.5mm²solid/flexible
Cross-sectional area(max)
16mm²flexible
For mounting on
35mm DIN rail, according to EN 60715
Enclosure material
Red thermoplastic material, UL 94 V-0
Degree of protection
IP20
Size
4 modules
Certification
TUV




 

SEND INQUIRY