What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Type |
REP-MSG25T1+T2-255-1S |
The SPD according to IEC/EN 61643-11 |
I+II/T1+T2 |
Energy coordination with termini equipment (≤5m) |
T1+T2+T3 |
Nominal AC voltage(Un) |
230/400Vac(50/60Hz) |
Maximum continuous voltage(Uc) |
255Vac(50/60Hz) |
Lightning impulse current(10/350μs) limp (L-N/N-PE) |
25kA/50kA |
Specific energy (L-N/N-PE)(W/R) |
156.25kJ/ohms/312.50 kJ/ohms |
Nominal discharge current(8/20μs) ln(L-N/N-PE) |
25kA/50kA |
Maximum discharge current(8/20μs) Imax(L-N/N-PE) |
100kA /160kA |
Voltage protection level Up @ln |
≤1. 5kV |
Response time | ≤100ns |
Follow current extinguishing capability a.c. Ifi |
25kArms/100Arms |
Follow current limitation/Selectivity |
No tripping of a 32 A gG fuse up to 25kArms(prosp) |
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic |
≥440V/120min.-withstand |
Temporary overvoltage(TOV)(N-PE)(UT)-Characteristic |
≥1200V/200ms-withstand |
Additional abnormal voltage test:485Vac/50Hz for 24h |
withstand |
Let-Through-Energy in combination with an MOV S20K275(Iimp÷0...25kA 10/350μs) |
<0.5J |
Remote alarm contact |
NC/C, |
Remote alarm contact capability Un/In |
AC:250/0.5A DC:250V/0.1A; 75V/0.5A |
Remote alarm contact connecting wire |
Max. 1.5mm² or #16AWG |
Operating temperature range |
-40℃...+80℃ |
Fault indicator |
Green: Normal ; Red: Failure |
Cross-sectional area(min.) |
4mm²solid/flexible |
Cross-sectional area(max.) |
25mm²flexible |
For mounting on |
35mm DIN rail |
Enclosure material |
Red thermoplastic, UL 94 V-0 |
Degree of protection |
IP20 |
Size |
2 modules |
SEND INQUIRY
REP-MS25T1+T2-255-1S