What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Model
REP-BC25T1+T2-320-4S
The SPD according to IEC/EN 61643-11
I+II/T1+T2
Energy coordination with termini equipment (≤5m)
T1+T2
Response time
≤100ns
Nominal AC voltage(Un)
230/400Vac(50/60Hz)
Maximum continuous voltage(Uc)
320Vac(50/60Hz)
Lightning impulse current(10/350μs) limp (L-PE, N-PE)
25kA
Nominal discharge current(8/20μs) ln(L-PE, N-PE)
25kA
Maximum discharge current(8/20μs) lmax(L-PE, N-PE)
200kA
Specific energy(L-PE)/(N-PE)(W/R)
156.25kJ/ohms
Voltage protection level Up @ln
≤1. 5kV
Voltage protection level Up@6kV(1.2/50μs)
≤1.0 kV
Follow current extinguishing capability a.c. Ifi
25kA rms
Follow current limitation/Selectivity
No tripping of a 32 A gG fuse up to 25kArms(prosp)
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
≥440V/120min.-withstand
Additional abnormal voltage test:485Vac/50Hz for 24h
Withstand
Let-Through-Energy in combination with an MOV S20K275(Iimp=2.5...25kA)
<0.5J
Remote alarm contact
NC/C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm² or #16AWG
Operating temperature range
-40℃...+80℃
Fault indicator
Light-off: Normal ; Light-on: Failure
Cross-sectional area(min)
1.5mm²solid/flexible
Cross-sectional area(max)
35mm²flexible
For mounting on
35mm DIN rail
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
IP20
Size
8 modules
REP-(BC25T1+T2-320-4S)144mm