Surge Protector for AC Power Supply System (T1+T2)

PRODUCT DETAILS

Features

  • Combination T1+T2 SPD surge protector.
  • Non exhausting encapsulated spark gap technology.
  • High follow current extinction and limitation due to no follow current.
  • Reliable supervision due to new LTR energy control technology.
  • With remote signaling contact optional and failure indicator.

Datasheet

Model
REP-BC25T1+T2-320-3S/4S
The SPD according to IEC/EN 61643-11
I+II/T1+T2
Energy coordination with termini equipment (≤5m)
T1+T2+T3
Response time
≤100ns
Maximum continuous voltage(Uc)
320Vac
Lightning impulse current(10/350μs) limp (L-PE, N-PE)
25kA/100kA
Nominal discharge current(8/20μs) ln(L-PE, N-PE)
25kA/100kA
Maximum discharge current(8/20μs) lmax(L-PE, N-PE)
200kA
Specific energy(L-PE)/(N-PE)(W/R)
156.25kJ/ohms
Voltage protection level Up @ln
≤1.5kV
Follow current extinguishing capability a.c. Ifi (L-N/N-PE)
25kA rms/100A rms
Follow current limitation/Selectivity
No tripping of a 32 A gG fuse up to 25kArms(prosp)
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
440V/120min.-withstand
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
1200V/120ms.-withstand
Additional abnormal voltage test:485Vac/50Hz for 24h
Withstand
Let-Through-Energy in combination with an MOV S20K275(Iimp=2.5...25kA)
<0.5J
Remote alarm contact 
NC/C,
Remote alarm contact capability Un/In
AC:250/0.5A        DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm²  or #16AWG
Operating temperature range  
-40℃...+80℃
Fault indicator
Light-off: Normal ; Light-on: Failure
Cross-sectional area(min)
1.5mm²solid/flexible
Cross-sectional area(max)
35mm²flexible
For mounting on
35mm DIN rail
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
IP20
Size
8 modules




 