What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Model
REP-MS15T1+T2-320-3S
The SPD according to IEC/EN 61643-11
I+II/T1+T2
Energy coordination with termini equipment (≤5m)
T1+T2+T3
Nominal AC voltage(Un)
230/400Vac(50/60Hz)
Response time
≤100ns
Maximum continuous voltage(Uc)
320Vac(50/60Hz)
Lightning impulse current(10/350μs)limp[L-N,N-PE]
15kA/50kA
Nominal discharge current(8/20μs)In[L-N,N-PE]
15kA/50kA
Voltage protection level Up @In
≤1.5kV
Specific energy[L-N,N-PE]
156.25KJ/ohms/625.00KJ/ohms
Follow current extinguishing capability a.c. Ifi
25kArms/100Arms
Follow current limitation/Selectivity
No tripping of a 32 A gG fuse up to 25kArms(prosp)
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
≥440V/120min.-withstand
Temporary overvoltage(TOV)(N-PE)(UT)-Characteristic
≥1200V/200ms-withstand
Additional abnormal voltage test:485Vac/50Hz for 24h
Withstand
Let-Through-Energy in combination with an MOV S20K275(Iimp÷0...25kA 10/350μs)
<0.5J
Remote alarm contact
NC/C,
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm² or #16AWG
Operating temperature range
-40℃...+85℃
Fault indicator
Green: Normal ; Red: Failure
Cross-sectional area (min)
1.5mm²solid/flexible
Cross-sectional area (max)
35mm²stranded/25mm²flexible
For mounting on
35mm DIN rail
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
IP20
Size
4 modules
SEND INQUIRY