SPD for Street Lighting

PRODUCT DETAILS

Features

  • Three items optional, already attained CB certificate.
  • Y circuit connection, offer full protection (L-N; N-PE; L-PE).
  • Mechanical disconnection and light indicator optional.
  • High discharge capacity in a certain small size.

  • Installation: wired connection and mounting optional.

  • Protection mode: in series and in parallel optional.

Datasheet

Model REP-MP5S 
REP-MP10
The SPD according to IEC61643:11
III/T3
III/T3
Nominal AC voltage (Un)
220-227Vac
230Vac
Maximum continuous voltage (Uc)
420Vac
275/385Vac
Nominal discharge current(8/20μs)In   
5kA
10kA
Maximum discharge current(8/20μs)Imax
10kA
20kA
Voltage protection level(Up)
(L-N)<1.5kV;(N-PE)<1.0kV
<1.8kV;<1.5kV
Response time
(L-N)≤25ns   (N-PE)≤100ns
Operating temperature range
-40℃~+80 ℃ 
Enclosure material
Flame retardant material  UL94-V0
Degree of protection
IP20
Failure indication
Green: Normal; Red: Failure
Remote alarm contact
Remote alarm contact optional


Standard

1. IEC 61643:11-2016
2. UL 1449 4th



    

REP-MP5S                      REP-MP10 (Y Circuit Connection)

 