What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Model
REP-SP05
REP-SP12
REP-SP24
REP-SP32
REP-SP48
REP-SP60
Nominal d.c. voltage (UN)
5V
12V
24V
32V
48V
60V
Max. continuous operating d.c. voltage (UC)
6V
15V
36V
42V
54V
70V
Load current insertion
200mA
200mA
200mA
1000mA
1000mA
1000mA
Nominal discharge current (8/20 μs) (In)
5kA
Max discharge current (8/20 μs) (Imax)
10kA
Voltage protection level (Up@ln) (L-L)
≤15V
≤27V
≤55V
≤85V
≤100V
≤270V
Voltage protection level (Up@In) (L-PE)
≤600V
≤600V
≤600V
≤600V
≤600V
≤600V
Insertion resistance
0.2Q
0.2Q
0.2Q
0.2Q
0.2Q
0.2Q
Installation rail
35mm DIN60715
Operating temperature range (TU)
-40 °C~+80°C
Degree of protection
Ip20
Enclosure material
PBT
Test standards
IEC61000-4-5; IEC61643:21
Online Replacement
Yes
REP-SP
Basic circuit diagram
Dimension drawing(mm)1P