T1 Surge Protector

PRODUCT DETAILS

Features

  • Class B / Type1 surge protector SPD.
  • Sealed metal spark gap technology coordinated with MOV technology.
  • High follow current extinction and limitation due to no follow current technology.
  • LTR energy control technology without additional cable length.

Datasheet

Model REP-B15
REP-B25
REP-B50
REP-B100NPE
The SPD according to IEC61643:11
T1/I
T1/I
T1/I
T1/I
Nominal AC voltage (Un)
230/400Vac(50/60Hz)
230/400Vac(50/60Hz)
230/400Vac(50/60Hz)
230/400Vac(50/60Hz)
Maximum continuous voltage (Uc)
320Vac(50/60Hz)
320Vac(50/60Hz)
320Vac(50/60Hz)
320Vac(50/60Hz)
Lightning impulse current (10/350μs)limp
15kA
25kA
50kA
100kA
Nominal discharge current (8/20μs)In
15kA
25kA
50kA
100kA
Maximum discharge current (8/20μs)Imax
160kA
160kA
160kA
200kA
Voltage protection level (Up)
≤1.5kV
≤1.5kV
≤1.5kV
≤2.0kV
Response time
100ns
100ns
100ns
100ns
Operating temperature range
-40℃~+80℃
Technical features
Sealed metal spark gap technology
Response time
≤100ns
Remote alarm contact
Remote alarm contact optional
Degree of protection
IP20
Failure indication
Light-off: Normal ; Light-on: Failure
Enclosure material
Flame retardant material,UL94-V0

Installation location

Standard

1. IEC 61643: 11-2016
2. UL 1449 4th

     


Side (mm)                                                                                Front (mm)


                                   
Basic Diagram (3+1)




 

SEND INQUIRY
GENERAL LOOK

         

           

           

Installation Diagram

Installation Details

Failure Indication


Related Product
HomeEmailContact