Surge Protectors for AC Power Supply System (T1)

PRODUCT DETAILS

Features

  • Type1 surge protector SPD.
  • Non exhausting encapsulated spark gap technology coordinated with MOV technology.
  • High follow current extinction and limitation due to no follow current technology.
  • LTR energy control technology, directly coordinated to Type 2 SPD without additional length.

Datasheet

Model REP-B15
REP-B15
REP-B15
REP-B15
The SPD according to IEOEN 61643
I/T1
I/T1
IVT1
I/T1
Nominal AC voltage(Un)
230/400Vac(50/60Hz)
230/400Vac(50/60Hz)
230/400Vac(50/60Hz)
230/400Vac(50/60Hz)
Maximum continuous voltage(Uc)
320Vac(50/60Hz)
320Vac(50/60Hz)
320Vac(50/60Hz)
320Vac(50/60Hz)
Lightning impulse current (10/350μs)limp
15kA
25kA
50kA
100kA
Nominal discharge current(8/20μs)ln
15kA
25kA
50kA
100kA
Maximum discharge current(8/20μs)lmax
160kA
160kA
160kA
200kA
Voltage protection level(Up)@ln
≤1. 5kV
≤1. 5kV
≤1. 5kV
≤2.0kV
Voltage protection level Up@6kV(1.2/50μs)
≤1. 0KV
Operating temperature range
-40℃~+80℃
Response time
≤100ns
Remote alarm contact
Remote alarm contact optional
Degree of protection
IP20
Failure indication
Light-off: Normal ; Light-on: Failure
Enclosure material
Thermoplastic; extinguishing degree UL94-V0
Technical feature
No exhausting encapsulated spark gap technology





 

SEND INQUIRY
GENERAL LOOK

                                

  36mm(2P) (L-N/PE) (N-PE)                                   72mm(4P) (1+1) (2+0)                                                     108mm(6P) (3+0)

144mm(8P)  (3+1) (4+0)

 

Dimension drawing(mm)2P

 

Basic circuit diagram



Related Product
HomeEmailContact