What's App:+86 13923097393 E-mail:info@xierli.com
PRODUCT DETAILS
Features
Datasheet
Type
REP-MSG25T1+T2-255-1S
The SPD according to IEC/EN 61643-11
I+II/T1+T2
Energy coordination with termini equipment (≤5m)
T1+T2+T3
Nominal AC voltage(Un)
Maximum continuous voltage(Uc)
255Vac(50/60Hz)
Lightning impulse current(10/350μs) limp (L-N/N-PE)
25kA/50kA
Specific energy (L-N/N-PE)(W/R)
Nominal discharge current(8/20μs) ln(L-N/N-PE)
25kA/50kA
Maximum discharge current(8/20μs) Imax(L-N/N-PE)
100kA /160kA
Voltage protection level Up @ln
≤1. 5kV
Follow current extinguishing capability a.c. Ifi
Follow current limitation/Selectivity
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
Temporary overvoltage(TOV)(N-PE)(UT)-Characteristic
Additional abnormal voltage test:485Vac/50Hz for 24h
<0.5J
NC/C,
AC:250/0.5A DC:250V/0.1A; 75V/0.5A
Max. 1.5mm² or #16AWG
Operating temperature range
-40℃...+80℃
Fault indicator
Green: Normal ; Red: Failure
Cross-sectional area(min.)
Cross-sectional area(max.)
For mounting on
35mm DIN rail
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
Size
230/400Vac(50/60Hz)
156.25kJ/ohms/312.50 kJ/ohms
Response time
≤100ns
25kArms/100Arms
No tripping of a 32 A gG fuse up to 25kArms(prosp)
≥440V/120min.-withstand
≥1200V/200ms-withstand
withstand
Let-Through-Energy in combination with an MOV S20K275(Iimp÷0...25kA 10/350μs)
Remote alarm contact
Remote alarm contact capability Un/In
Remote alarm contact connecting wire
4mm²solid/flexible
25mm²flexible
IP20
2 modules
SEND INQUIRY
REP-MS25T1+T2-255-1S