What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
System Earthing Arrangements
All System Earthing Arrangements (SEA) provide equivalent protection of life and property. However each has certain advantages and inconveniences in other terms that may be important for a given installation.
In both commercial and industrial applications, needs change, and it is becoming increasingly important to choose the right system earthing arrangement, according to rigorously defined working practices, in order to ensure the cohabitation of "high and low currents" and satisfy the operator’s requirements.
Following a review of the risks related to installation insulation faults affecting the safety of persons and equipment, this Technical Guide describes the three types of system earthing defined by standards IEC 60364 and NF C 15.100.
Each system earthing arrangement is examined in terms of safety and availability, as well as for its protection against overvoltages and electromagnetic disturbances.
Terminology
In this chapter the electric shock and electrocution risks are specified for the various system earthing arrangements, as defined by the International Electrotechnical Committee in standard IEC 60364.
The system earthing arrangement in LV characterises the earthing of the secondary of the HV/LV transformer and the earthing of the exposed conductive parts of the installation. Identification of the types of system earthing arrangements is thus defined by 2 letters:
T for "earthed";I for "unearthed" (or "isolated")
T for "directly" earthed; N for "connected to earthed neutral" at the origin of the installation.
The combination of these two letters gives three possible configurations:
Transformer neutral Exposed conductive parts
if T T or N
if I T
i.e. TT, TN and IT.
(1) ECP: exposed conductive part.
Note 1 :
The TN system, according to IEC 60364 and standard NF C 15-100, has several
sub-systems:
Note that the TN-S is compulsory for systems with conductors of a cross-section y 10 mm2 Cu.
Note 2 :
Each system earthing arrangement can be applied to an entire LV electrical installation. However, several arrangements can jointly exist in the same installation.
Example of a simplified earth leakage current (Id) calculation
TT In the presence of an insulation fault, the fault current Id is limited for the most part by the earthing resistances (if the earthing connections for the exposed conductive parts and for the neutral are not combined).
This fault current induces a fault voltage in the load earthing resistances.
Since the earthing resistances are normally low and of the same order of magnitude (@10 W), this voltage of around Uo/2 is dangerous.
The part of the installation concerned by the fault must therefore be automatically disconnected by an RCD.
TN In the presence of an insulation fault, the fault current Id is only limited by the impedance of the fault loop cables.
For 230/400 V systems, this voltage of the order of Uo/2 (if RPE = Rph) is dangerous as it is greater than the limit safety voltage, even in dry environments (UL = 50 V). The installation or part of the installation must then be immediately and automatically de-energised by an RCD.
As the insulation fault is similar to a phase-toneutral short-circuit, breaking is performed by the overcurrent protection devices.
IT Behaviour on the 1st fault
Behaviour on the 2nd fault
The double fault is a short-circuit (as in TN). Breaking is performed by the overcurrent protection devices.
Function
TT This system sustains the "earth fault" ... but limits the consequences by implementing residual current devices which detect the earth fault before it becomes a short-circuit. This is the principle of the TT "directly earthed neutral" systems which allow the addition of extra outgoers by simply combining them with an RCD.
It is the safety champion!
v built into or added to the circuit breaker and switch with the 0.5 to more than 100 A Multi 9 range
Ø built into the circuit breaker with the 100 to 630 A Vigi module
Ø built into the circuit breaker with the insulation monitoring module
Ø with separate toroid with the 100 to 6300 A
Vigirex devices which indicate absence of auxiliary supply source without causing tripping (avoids resets), and also warn the user of the insulation drop without causing tripping, by means of an early warning contact which is activated at half of the displayed threshold.
For example: set at 300 mA, it warns the user at 150 mA.
TN When a fault occurs, this system causes tripping of the SCPD (short-circuit protective device) to provide protection.This fault is similar to a short-circuit (very low fault loop impedance) and is thus violent and destructive.The circuit breaker therefore trips on the 1st fault.
Ø Multi 9
Ø Compact
Ø Masterpact.
IT This system renders the fault inoffensive. It consists of attacking the cause rather than the effect by limiting the fault current to a few mA.
In an IT unearthed neutral or impedant neutral system, as the fault is not dangerous, there is no need to trip and operation can continue.
It is the electrical power availability champion!