REP-MPG15T1+T2-320

PRODUCT DETAILS

Features

  • Type1+Type2  pluggable surge protector
  • No exhausting encapsulated spark gap technology
  • Low protection level≤1.5kV
  • LTR energy control technology, directly coordinated to next SPD without additional length


Datasheet

Model REP-MPG15
The SPD according to IEC61643-1/11
Type1+Type2
Energy coordination with terminal equipment(≤5m)
Type 1+Type2+ Type3
Nominal AC voltage (Un)
230Vac
Maximum continuous voltage (Uc and Ut)
320Vac Ut=485V(L-N) for 6 Hours

Maximum continuous voltage (Uc and Ut)

320Vac Ut=485V(L-N) for 6 Hours
Lightning impulse current(10/350μs)Iimp
15kA
Nominal discharge current (8/20μs)In
15kA
Maximum discharge current (8/20μs)Imax
60kA
Voltage protection level (Up) [L-N]
≤1.5 KV
Voltage protection level [N-PE] Up
≤1.5 KV
Response time
100ns 
Cross-sectional area (min).
1.5 mm² solid/flexible
Cross-sectional area (max).
35 mm² flexible
Temporary overvoltage(TOV)[L-N] (UT)-Characteristic
440V/ 120min.-withstand
Additional abnormal voltage test:485Vac/50Hz for 24h
withstand
Operating temperature range
-40℃~+80℃
For mounting on
35 mm DIN rail
Remote alarm contact
Remote alarm contact optional
Shell material
Red or black optional thermol plastic, UL 94 V-0
Degree of protection
IP20
Work/Fault indicator
Green: Normal ; Red: Failure
Back-up fuse
315A gL/gG
Type of remote signaling contact
Changeover contact


SEND INQUIRY
GENERAL LOOK





Related Product