REP-BC25T1+T2-320-1S/2S
The SPD according to IEC/EN61643
Type 1+Type 2
Max. continuous operating voltage (a.c.)Uc
320Vac
Lightning impulse current(10/350μs)limp(L-N/N-PE)
25kA/100kA
Nominal discharge current(8/20μs)In(L-N/N-PE)
20kA/100kA
Maximum discharge current(8/20μs) Imax(L-N/N-PE)
120kA
Voltage protection level Up
≤1.5kV
Response time(t.)
≤100ns
Follow current extinguishing capability a.c. Ifi(L-N/N-PE)
25kArms/100Arms
Follow current limitation/Selectivity
No tripping of a 20 A gG fuse up to 25KArms(prosp)
Temporary over voltage (TOV)(UT)-Characteristic
400V/120 min.-withstand
Operating temperature range
-40℃...+80℃
Remote alarm contact
NO/NC/C,Isolated Form C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A;75V/0.5A
Remote alarm contact connecting wire
Max.1.5mm² or#16AWG
Cross-sectional area (min.)
1.5 mm²solid/flexible
Cross-sectional area (max.)
35mm²stranded/35mm²flexible
For mounting on
35 mm DIN rail
Degree of protection
IP20
Failure indicator
Light-off: Normal ; Light-on: Failure
Enclosure material
Red thermoplastic ,UL 94 V-0
Size
8modules