What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
Model
REP-PV1200
The SPD according to IEC 61643-11:2018, EN 61643-11:2019
Type 2
Response time (t.)
≤25ns
1200V
Short circuit tolerance (Iscpv)
2000A
20kA
Maximum discharge current(8/20μs) [(DC+/DC-)→PE] Imax
40kA
Voltage protection level(Up)
≤4.5kV
63A/35kA
Leakage current
≤10μΑ
Internal overheating circuit breaker
Built-in
Operating temperature range
-40℃...+80℃
Work/Fault indicator
Green: Normal ; Red: Failure
Connecting wire
≥4mm²
Installation
35mm DIN rail, according to EN 60715
Enclosure material
Red thermoplastic material, UL94 V-0
Degree of protection
IP20
Size
4 modules
REP-PV1200