Model |
REP-DC175-V |
The SPD according to IEC 61643-31:2018, EN 61643-31:2019
|
Type 2 |
Response time(t.) |
25ns |
Protection mode
|
DC+ to DC- or DC+/- to PE
|
Maximum continuous operating voltage (DC) Uc |
≤175V
|
Short circuit tolerance (Iscpv) |
1000A |
Nominal discharge current(8/20μs) [(DC+/DC-)→PE] In
|
20kA |
Maximum discharge current(8/20μs) [(DC+/DC-)→PE] Imax |
40kA |
Voltage protection level(Up) |
≤0.8kV |
Recommended series connection overcurrent protector
|
63A/35kA |
Leakage current |
≤10μΑ |
Internal overheating circuit breaker |
Built-in |
Operating temperature range |
-40℃...+80℃ |
Work/Fault indicator |
Green: Normal ; Red: Failure |
Connecting wire |
≥4mm² |
Installation |
35mm DIN rail, according to EN 60715 |
Enclosure material |
Red thermoplastic material, UL 94 V-0 |
Degree of protection |
IP20 |
Size |