Type1+Type2+Type3 SPD

PRODUCT DETAILS

Features

  • Small combination T1+T2+T3 SPD surge protector only 72mm for three phases.
  • Spark gap technology with high surge capacity and low voltage protection level.
  • High follow current extinction and limitation due to no follow current.
  • Reliable supervision due to new LTR energy control technology.
  • With remote signaling contact optional and mechanical failure indicator.

Datasheet

Model
REP-MWG15T1+T2+T3-255-3S  
The SPD according to IEC/EN 61643-11
I+II+III+/T1+T2+T3
Energy coordination with termini equipment (≤5m)
T1+T2+T3
Response time
≤100ns
Maximum continuous voltage(Uc)
255Vac(50/60Hz)
Lightning impulse current(10/350μs) limp (L-PE, N-PE)
15kA/50kA
Nominal discharge current(8/20μs) ln(L-PE, N-PE)
15kA/50kA
Maximum discharge current(8/20μs) lmax(L-PE, N-PE)
100kA/120kA
Specific energy(L-PE)/(N-PE)(W/R)
156.25kJ/ohms
Open circuit voltage (1.25/50μs) (Uoc)
6kV
Voltage protection level Up @ln
≤1. 5kV
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
≥440V/120min.-withstand
Temporary overvoltage(TOV)(N-PE)(UT)-Characteristic
≥1200V/120ms.-withstand
Additional abnormal voltage test:485Vac/50Hz for 24h
Withstand
Backup fuse(only required if not already provided in mains)
≤400A gL/gG
Remote alarm contact 
NC/C,
Remote alarm contact capability Un/In
AC:250/0.5A        DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm²  or #16AWG
Operating temperature range  
-40℃...+80℃
Work/Fault indicator Green: Normal; Red: Failure
Cross-sectional area(min.)
1.5mm²solid/flexible
Cross-sectional area(max.)
35mm²flexible
For mounting on
35mm DIN rail
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
IP20
Size
4 modules




 

SEND INQUIRY
GENERAL LOOK

REP-MWG15T1+T2+T3-255-3S

        

Dimension drawing(mm)

Basic circuit diagram



Related Product