BC25 Type1+Type2 Power Surge Protector

PRODUCT DETAILS

Features

  • Combination T1+T2 SPD surge protector for single phase.
  • Non exhausting encapsulated spark gap technology with extremely high surge capacity.
  • High follow current extinction and limitation due to no follow current.
  • Reliable supervision due to new LTR energy control technology.
  • With remote signaling contact optional and failure indicator.

Datasheet

Model
REP-BC25T1+T2-320-1S/2S
The SPD according to IEC/EN 61643-11
I+II/T1+T2
Energy coordination with termini equipment (≤5m)
T1+T2+T3
Response time
≤100ns
Maximum continuous voltage(Uc)
320Vac
Lightning impulse current(10/350)limp[L-N,N-PE]  
15kA/60kA
Nominal discharge current(8/20)In[L-N,N-PE]
15kA/60kA
Maximum discharge current(8/20)Imax[L-N,N-PE]   
100/120kA
Voltage protection level Up @In
≤1.5kV
Follow current extinguishing capability a.c. Ifi(L-N/N-PE)
25kA rms/100A rms
Follow current limitation/Selectivity
No tripping of a 32 A gG fuse up to 25kArms(prosp)
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic
440V/120min.-withstand
Temporary overvoltage(TOV)(N-PE)(UT)-Characteristic
1200V/200ms-withstand
Additional abnormal voltage test:485Vac/50Hz for 24h
Withstand
Let-Through-Energy in combination with an MOV S20K275(Iimp=2.5...25kA)
<0.5J
Remote alarm contact 
NC/C
Remote alarm contact capability Un/In
AC:250/0.5A DC:250V/0.1A; 75V/0.5A
Remote alarm contact connecting wire
Max. 1.5mm²  or #16AWG
Operating temperature range  
-40℃+80℃
Fault indicator
Light-off: Normal ; Light-on: Failure
Cross-sectional area (min)
1.5mm²solid/flexible
Cross-sectional area (max)
35mm²flexible
For mounting on
35mm DIN rail
Enclosure material
Red thermoplastic, UL 94 V-0
Degree of protection
IP20
Size
4 modules




 

SEND INQUIRY
GENERAL LOOK

REP-BC25T1+T2-320-1S                                  REP-BC25T1+T2-320-2S




Related Product
HomeEmailContact